**What is the Operating Mode of the Inverter?**
Before starting the inverter, it's essential to understand its operating modes and perform necessary tests. This guide outlines the steps for testing and setting up an inverter, including no-load and load tests, as well as specific procedures for different brands like Fuji and Yaskawa.
**First, Perform a No-Load Current Test on the Inverter**
1. Ground the inverter’s ground terminal to ensure safety.
2. Connect the inverter’s power input to a power supply through a leakage protection switch.
3. Check the inverter’s factory display. If it shows errors, reset it; otherwise, return it for inspection.
4. Familiarize yourself with the inverter’s operation keys. Most inverters have six main keys: Run (RUN), Stop (STOP), Programming (PROG), Data Entry (DATAPENTER), Up (▲), and Down (▼). Some models also include function keys like Monitor (MONITOR), Reset (RESET), Jog, and Shift (SHIFT).
**Second, Run the Motor at No Load**
1. Set the motor’s power and number of poles, considering the inverter’s working current.
2. Configure the inverter’s maximum output frequency, base frequency, and torque characteristics. Choose the appropriate V/f curve based on the load type—constant torque or variable torque.
3. Adjust the torque settings for fan and pump loads to improve low-speed performance and prevent stalling.
4. Set the inverter to keyboard operation mode and test the start/stop function by pressing the RUN and STOP buttons.
5. Understand the inverter’s protection codes and check the thermal relay and overload settings. Adjust them if necessary according to the manufacturer’s instructions.
**Third, Conduct a Load Test Run**
1. Manually operate the inverter panel to observe the motor’s start/stop process and check for any abnormalities.
2. If overcurrent occurs during motor start/stop, adjust the acceleration and deceleration times. These should be set based on the motor’s inertia and load to avoid stalling.
3. If the inverter still trips, try changing the run curve from linear to S-shaped or U-shaped to match the load characteristics.
4. Increase the maximum current protection value slightly but never disable it completely. Maintain at least 10–20% margin for safety.
5. If the problem persists, consider using a higher-power inverter.
6. If the motor fails to reach the preset speed during startup, recheck all settings and configurations.
**Five Types of Inverter Operation Methods (1)**
**1. Fuji Inverter Operation**
The operation of a Fuji inverter involves several key steps:
- Press the PRG key to access the menu.
- Use the FUNC key to navigate through the options.
- Use the ∧ and ∨ keys to select items.
- Enter data using the SHIFT > key to modify specific bits.
- Save the changes by pressing FUNC.
- Return to the main screen by pressing RESET and PRG.
**2. Fuji Inverter Settings**
To configure the parameters:
- Press PRG to enter the menu.
- Navigate using FUNC and ∧/∨.
- Modify values using SHIFT >.
- Save settings with FUNC.
- For self-learning, set parameter F02 to 0, press FWD/RWD, then stop and set F02 to 1.
**Five Types of Inverter Operation Methods (2)**
**1. Yaskawa Inverter**
Yaskawa inverters are widely used in industrial applications. They offer advanced control features and user-friendly interfaces.
**2. Yaskawa Inverter Settings**
- **Language Change:** Access the Programming menu, change A1-00 to 0, and save the setting.
- **Auto-Tuning Process:** Enter the AUTO-TUNING menu, adjust parameters, and press RUN to start the tuning process. Once complete, the inverter will display “TUNE SUCCESS.â€
These steps help users configure and operate various types of inverters effectively, ensuring safe and efficient performance. Always refer to the manufacturer’s manual for detailed specifications and guidance.